How Do You Test A 3 Phase Motor With A Megger?

by | Last updated on January 24, 2024

, , , ,
  1. Turn off the power supply to the , usually accomplished by switching the circuit breaker. …
  2. Place one megger probe to the any mounting bolt on the breaker box to test for grounding continuity, then touch the other probe to a motor terminal.
  3. Crank the handle for about a minute, and notice the resistance reading.

How do you test a 3 phase motor for insulation?


Using a multimeter

, check the continuity of motor winding from phase to phase ( U to V, V to W , W to U ). Each phase to phase must have a continuity if winding is OK. If any particular phase fails the continuity test, your motor is probably burnt.

How do you test a motor Megger?


Press the test button on megger

, the megger will generate current. This current flows through cable, the resistance in scale is noted which ranges between 35 to 100 Mega Ohms. Note to maintain this contact for 30 to 60 seconds. Acceptable IR for electrical cable = 1 Mega Ohm for 1000 V.

What is a good Megger reading for a motor?

The rule may be stated:

Insulation resistance should be approximately one megohm for each 1,000 volts of operating voltage

, with a minimum value of one megohm. For example, a motor rated at 2,400 volts should have a minimum insulation resistance of 2.4 megohms.

How do you know if a 3 phase motor is bad?

Check all three wires singly T1,T2,T3 (all three phases)

to the ground wire

. Readings should be infinite. If its zero or reads any continuity at all, then a problem exists with either the motor or cable . If it is go directly to the motor and disconnect from cable and check motor and the cable separately.

How do you ohm out a 3 phase motor?

The reading should be between

0.3 to 2 ohms

. If it is 0, there is a short. If it is over 2 ohms or infinite, there is an open. You can also dry the connector and retest to possibly get more accurate results.

What is considered a bad Megger reading?

Turn on and read the meter. Anything reading between 2 megohms and 1000 megohms is usually considered a good reading, unless other problems have been noted.

Anything less than 2 megohms indicates an

insulation problem.

How many ohms should a motor read?

A good motor should read

less than 0.5 ohms

. Any value greater 0.5 ohms indicate trouble with the motor.

What is a good Megger reading for a 480v motor?

Our minimum meg readings are 1.5 megs for 480 volt motors at 1000 volt meg. (That would be 1.5 million ohms to ground resistance.) 1.5 to 20 is fair.

20 to 50 is good

.

What is a bad insulation resistance reading?

The purpose of the IR test is to check for damaged insulation, this can be mechanical damage or damage by heat, (overloaded cables), readings

less than 2 Mohm indicate

damaged insulation, readings of 2-50 Mohm are indicative of long circuit lengths, moisture and contamination and do not indicate the insulation quality, …

How do you check if a motor is burned out?

To test your motor for short to ground, you'll need to

set the multimeter to ohms and disconnect the motor from its power source

. Then inspect each wire and look for infinite readings. Alternatively, if you get a reading of 0, you might have a cable issue.

How many ohms should a 3 phase motor have?

The reading should be between

0.3 to 2 ohms

. If it is 0, there is a short. If it is over 2 ohms or infinite, there is an open. You can also dry the connector and retest to possibly get more accurate results.

What is the minimum insulation resistance of a motor?

Insulation resistance should be approximately

one megohm for each 1,000 volts of operating voltage

, with a minimum value of one megohm. For example, a motor rated at 2,400 volts should have a minimum insulation resistance of 2.4 megohms.

How do you calculate the resistance of a motor?

As I understand it, calculating the resistance is possible by

applying a small current to the motor and measuring the voltage with a multimeter

. That's exactly what a digital multi-meter does when on an Ohms range. Just use a DMM and measure with the motor unpowered and the armature in various positions.

How do you test a 3 phase motor inductance?

Inductance is measured by

applying a sinusoidal signal

and then measuring the phase difference between the voltage wave form and current wave form. Connect the motor to a function generator or the such. Place a resistor in series between the motor and the function generator on the negative side.

How do you know if a motor is bad on a multimeter?

With a multimeter set to low ohms (usually 200), test between each winding terminal and the metal casing of the motor. If there is any reading on any of these then the motor is bad, do not use it. You may find that when it

runs ungrounded that the casing becomes live at up to supply voltage

.