How Often Should Fire Dampers Be Inspected?

by | Last updated on January 24, 2024

, , , ,

NFPA 105(10), Sec. 6.5. 2 requires that each damper be tested and inspected 1 year after installation and that the test and inspection frequency then be every 4 years , except for hospitals, where the frequency is allowed to be every 6 years.

How often do fire dampers need to be inspected UK?

How Often Should You Conduct Fire Damper Testing? According to British Standard 9999:2017, all fire dampers need to be tested after installation by a competent person and then annually moving forward .

Is fire damper testing a legal requirement?

Under the Regulatory Reform (Fire Safety) Order it is a legal requirement to test fire dampers at regular intervals in accordance with fire safety in the design, management and use of buildings code of practice (BS:9999 2017), using a method known as ‘drop testing’.

How are fire dampers tested?

In NFPA 80, section 19.3 Operational Test, fire damper testing is detailed. The essential test is that the damper will open and close and no obstructions are present . NFPA 72 9 is referenced when any smoke detection is present. The operation must be under the airflow conditions that the system will encounter.

What is a damper check?

noun A door or slide by which cold air may be admitted to the base of the flue or chimney behind the fire and without passing through or over the latter.

Where are fire dampers required?

Generally, fire dampers are required where air ducts penetrate walls that are rated for 2-hours or more . They are needed in all air transfer openings (non-ducted) in rated walls, regardless of the rating. And they are required at some, but not all penetrations of rated floor assemblies and shaft enclosures.

What are fire dampers used for?

Fire Dampers are used in air transfer openings, ducts and other places where fire rated structures (e.g. walls, floors or other fire barriers) are penetrated.

What are fire dampers in a building?

So what is a fire damper ? Simply as the name suggests it’s a fire protection device , a tested metal sleeve mechanical device that will stop a fire from travelling through a fire rated wall or slab – when installed correctly, as per the manufactures test report and in a suitable constructed and rated wall, slab.

What does BS EN 1366 cover in terms of fire resistance testing?

The BS EN 1366-3:2009 test standard is the Fire Resistant tests for service installations. ... The purpose of BS EN 1366-3 is to assess: The effect of such penetrations on the integrity and insulation performance of the separating element concerned . The integrity and insulation performance of the penetration seal .

What is bs9999?

BS 9999: Code of practice for fire safety in the design, management and use of buildings, provides a best practice framework for fire safety. It is aimed at designers and architects. It is intended for: Architects, surveyors and designers. Facilities and building managers and building control officers.

How long do fire dampers last?

NFPA 105(10), Sec. 6.5. 2 requires that each damper be tested and inspected 1 year after installation and that the test and inspection frequency then be every 4 years , except for hospitals, where the frequency is allowed to be every 6 years.

How much does a fire damper cost?

The average cost of fire damper testing and inspections is between $40-$150 per fire damper .

Do fire smoke dampers require power?

Smoke dampers are motorized with electric or pneumatic actuators and may be controlled by a smoke or heat detector signal, a fire alarm signal, or by the building control system to accomplish the intent of the design.

Can fire dampers be painted?

Damaged or fused links can cause a damper to close, shutting off airflow unnecessarily, or hold the damper open and prevent it from fully closing when needed. During construction or remodeling of a facility, fusible links can be painted over , which will affect their ability to melt at the proper temperature.

Who inspects fire dampers?

Regular maintenance of fire and smoke dampers is required by the National Fire Protection Association (NFPA) and the International Building and Fire Codes and is enforced by Authorities Having Jurisdiction (AHJ’s) such as the Joint Commission, fire marshals and insurance risk auditors .

Do you need a fire damper in a one hour rated wall?

Q: Are fire dampers required in one-hour fire-rated walls if the facility is fully sprinkled? A: According to NFPA 90A (1999 edition), one-hour fire-rated barriers do not require fire dampers in fully ducted HVAC systems , unless the one-hour fire-rated barrier is a vertical shaft.

David Martineau
Author
David Martineau
David is an interior designer and home improvement expert. With a degree in architecture, David has worked on various renovation projects and has written for several home and garden publications. David's expertise in decorating, renovation, and repair will help you create your dream home.