Temp (F) Temp (C) Vapor Pressure (PSIG) | 89.6 32 165.56 | 93.2 34 175.71 | 96.8 36 186.3 | 100.4 38 197.32 |
---|
Are 407C and R22 pressures the same?
R407C has 6.60 % more pressure ratio than R22
. Lower pressure ratio was suggested for higher compressor efficiency. Joudi et al. (11) showed that the average compression ratio of R407C is higher by 3.7% & 5.6% for 1 TR and 2 TR system respectively than that of R22.
What is the normal operating pressure for 407C?
If this is so always evaporating above zero, 4 or 5 deg celcius, R407c will have a low pressure (suction ) of
about 50 psi.
and a high pressure ( discharge ) of about 280 psi, which is about 55 deg celcius, cooling cycle. Standing pressure ( system not running ) will depend on surrounding temperature of outdoor unit.
Should 407C be charged as a liquid?
Genetron® 407C must be
the only liquid charged into a system
to ensure proper refrigerant composition and system performance.
Can you charge 407C as a vapor?
8. Charge System with FreonTM 407C. … Once liquid is removed from the cylinder,
the refrigerant can be charged to the system as liquid or vapor as required
. Use the manifold gauge set or a throttling valve to flash the liquid to vapor if needed.
IS 407C a good refrigerant?
The
best replacement for R-22 Freon
is usually R-407c. It has a very low loss in capacity (0 – 5%) relative to R-22 and is less expensive than many other R-22 replacement refrigerants. If a system has R22 in it already you cannot use a replacement refrigerant to simply add to the R22.
What is a good superheat for 407C?
For R22 systems the superheat should be between 3°C and 5°C, for R407C systems the TX valve should be adjusted to achieve
6°C to 8°C
super heat. Systems for R407C must have a TX valve fitted which allows for this adjustment to be done.
Can 407C and R22 be mixed?
Mixing R22 with R407C or any other refrigerant. According to the 609 EPA rule,
mixing refrigerants is illegal
and anybody caught doing so will be heavily fined. … R22 is a HCFC chemical gas that create a chain reaction in the stratosphere and thin the ozone layer that protect us from the UV light of the sun.
What should my R22 pressures be?
R22 gauge pressure is 10.9 bar or
158.2 psi
. High side pressure typically varies by equipment and metering controls.
What is the suction and discharge pressure for R22?
For example, a high-efficiency condensing unit using R-22 typically operates with a
suction pressure of about 68 psi and a discharge pressure of about 250 psi
at an outdoor temperature of 95°F.
IS 407C Zeotropic?
R407C is a
zeotropic HFC refrigerant blend
of R125, R32 and R134a. R407C is predominantly used in commercial and residential air conditioning systems and has very similar properties to R22.
What oil is used with 407C?
R407C units will contain
polyolester oil (POE)
. Check the compressor label to confirm the type of oil in the system. For safe system operation it is essential to remove the mineral oil from the existing system, as R407C is not compatible with mineral oil.
IS 407C being phased out?
Among the HFCs and HFC-blend refrigerants affected by the regulations are several that are familiar to facility managers: R-404A, R-134a, and R-410A and R-
407C
, used to replace R-22. Under the rules, new chillers would no longer be produced using these refrigerants after Jan. 1, 2024.
How much does 407C refrigerant cost?
R407C Refrigerant Price per Pound
R407C is a non-ozone depleting refrigerant that contributes somewhat to global warming, even though it is still a preferable option to R22 coolant. On average, Refrigerant 407C price ranges
between $4 and $7 per pound
.
What should subcooling be for 407C?
Re: R407C Sub Cooling
anything from
5 to 10K
will be ok, if you have a larger condensor with subcoolcircuit you can even go as far as 12 – 14K subcool. Keep an eye on the superheat and the discharge superheat and see if they stay in range.
WHAT IS 407C Freon used for?
R-407C is a non-azeotropic mixed refrigerant composed of the three ingredients R-32, R-125, and R-134a, and was developed as a substitute refrigerant for R-22, used in
applications such as air conditioning equipment and chiller equipment for medium temperature ranges
.