Where Are Electrical Receptacles Not Permitted To Be Located?

by | Last updated on January 24, 2024

, , , ,

For example, a sun-room in a dwelling has no wall space because of floor-to-ceiling windows. Receptacles are not usually installed

in the ceiling

because receptacles located more than 5.5 feet (1.7 meters) above the floor cannot be counted as required receptacles.

Where is a receptacle not required?

GFCI protection is not required for receptacles that are not readily accessible, such as a ceiling-mounted receptacle for

a garage door opener

. Nor are they required for a receptacle on a dedicated branch circuit located and identified for a cord-and-plug-connected appliance, such as a refrigerator or freezer.

What is code for placement of electrical outlets?

The US National Electrical Code,

Section 210.52

, states that there should be an electrical outlet in every kitchen, bedroom, living room, family room, and any other room that has dedicated living space. They must be positioned at least every six feet measured along the floor line.

Where are receptacles located?

In botany, the receptacle refers to vegetative tissues

near the end of reproductive stems

that are situated below or encase the reproductive organs.

Where a receptacle is installed in a cabinet below a sink it is not permitted to be installed in?

Receptacles shall not be installed in a

face-up position

in or on countertop surfaces or work surfaces unless listed for countertop or work surface applications. N (2) Under Sinks. Receptacles shall not be installed in a face-up position in the area below a sink.

How many outlets can one GFCI protect?


There’s no limit

. A standard GFCI will protect up to 20 amps, drawn from any combination of receptacles, either the built-in one or any number of additional ones connected to its load terminals.

Can I put a GFCI anywhere in a circuit?


You can replace almost any electrical outlet with a GFCI outlet

. Correctly wired GFCIs will also protect other outlets on the same circuit. … The electrical code also requires GFCIs in unfinished basements, garages, most outdoor receptacles and places where construction activity occurs.

What is the height of electrical outlets from floor?

Standard Height for Outlet Boxes

The standard height for wall outlet boxes is

about 12 inches

from the top of the floor covering to the bottom of the receptacle box (or 16 inches to the top of the box).

What height do you run electrical wire?

When running cable through studs, drill all holes at the same height so that the cable is run level to the floor. Drill holes

6 to 8 in. above or below

all switch and receptacle boxes.

How far does an outlet have to be from a corner?

The National Electrical Code requires that you have an electrical outlet within

6 feet

of the corner of the wall and at least 12 feet from the same wall.

How many receptacles can you put on a 20 amp circuit?

The answer to the question how many outlets on a 20 amp circuit is

ten outlets

. Always comply with the 80% circuit and breaker load rule, allowing a maximum load of 1.5 amps per receptacle. Remember that your circuit, wire sizes, and outlets must be compatible to avoid overheating and electrical hazards.

Does every outlet in a kitchen need to be GFCI?


All countertop receptacle outlets must be protected by a GFCI device installed at the outlet

or by GFCI circuit breakers. A kitchen must have two 20-amp circuits for countertop appliances. There should be countertop receptacles installed so that no point along the counter is more than 2 ft. from an outlet.

How many outlets can be on a 15 amp breaker?

Technically, you can have as many outlets on a 15 amp circuit breaker as you want. However, a good rule of thumb is 1 outlet per 1.5 amps, up to 80% of the capacity of the circuit breaker. Therefore, we would suggest a

maximum of 8 outlets

for a 15 amp circuit.

Can outlets be installed facing up?

The electrical code allows outlets to be installed with the ground plug hole facing up, down or sideways. It’s

up to you

, there is no standard electric outlet orientation. So that means there really is no such thing as upside down outlets.

Can you install a receptacle face up?

A:

Any receptacle is permitted to be installed in

a face-up position in a countertop.

Which location is not required to be GFCI protected?

GFCI protection is not required for receptacles that are not readily accessible, such as a

ceiling-mounted receptacle for a garage door opener

. Nor are they required for a receptacle on a dedicated branch circuit located and identified for a cord-and-plug-connected appliance, such as a refrigerator or freezer.

David Martineau
Author
David Martineau
David is an interior designer and home improvement expert. With a degree in architecture, David has worked on various renovation projects and has written for several home and garden publications. David's expertise in decorating, renovation, and repair will help you create your dream home.